NAME
riello_ser - Driver for Riello UPS Protocol UPS equipment via serial port connections
SYNOPSIS
riello_ser -h
riello_ser -a UPS_NAME [OPTIONS]
Note
|
This man page only documents the hardware-specific features of the riello_ser driver. For information about the core driver, see nutupsdrv(8). |
SUPPORTED HARDWARE
riello_ser supports all recent Riello UPS, Aros UPS models which use the Riello UPS GPSER and SENTR protocols.
Older Riello UPS products are not supported.
EXTRA ARGUMENTS
You may need to tweak some settings, depending on the make and model of your UPS (see ups.conf(5)):
- localcalculation
-
When enabled, driver will calculate values of
battery.runtime
andbattery.charge
"locally" in the driver. This is for some Riello models which provide incorrect values in hardware readings, or none at all. This "local calculation" is done according to nominal battery capacity, nominal battery voltage, actual battery charge, maximum and actual UPS load.You may want to also configure default.battery.voltage.low and default.battery.voltage.high in case the built-in default range (from 10.7V to 12.9V) does not match your hardware, or give a shot to default.battery.voltage.nominal (e.g. 24) if your device does not serve that either.
NoteLead (PbAc) battery charge graph is not linear, so guesstimated charge value may not be perfectly accurate. However it should be good enough to determine battery actual status and roughly estimate the time it can still power the system. WarningThis keyword may be deprecated in future releases of the driver, in favor of runtimecal
and other settings which it requires (as seen in nutdrv_qx(8), blazer_ser(8) and blazer_usb(8) drivers).
AUTHOR
Massimo Zampieri
SEE ALSO
Related drivers
The core driver
Internet resources
The NUT (Network UPS Tools) home page: https://www.networkupstools.org/