The following document describes the standard UPS communication interface that Systems Enhancement Corporation has adopted.

Connector: D-Sub-9 Female

Communication Interface Pin Assignment

PIN NUMBER SIGNAL DESCRIPTION

1

Inverter Shutoff

The UPS shuts off when a high RS-232 level is applied to pin 1 for .5 seconds. The UPS responds to this signal, after a delay, and only during on-battery operations.

2

ByPass Active

UPS relay closes between pins 2 & 4 when the power supply has a failure or is being serviced and power is being provided to the system from the utility power line.

3

AC Fail (N.O.)

UPS relay closes between pins 3 & 4 when input power is lost.

4

Common

Switch common for pins 2, 3, 5, 6.

5

Low Battery (N.O.)

UPS relay closes between pins 5 & 4 when UPS battery has less than 2 minutes of life left.

6

UPS On

The UPS is powered on and is capable of providing power to the system.

7

TXD

RS-232 Transmit Data

8

RXD

RS-232 Receive Data

9

Ground

Communication Signal Ground

Note Pin 4 should be connected to ground

RS232 Technical Specification Summary

Connector:

9 pin, Type D, Female

Format:

ASCII 8 Bit, One Start Bit, One Stop Bit

Baud Rate:

Default 2400

Parity:

None

Duplex:

Full

Delimiters:

Carriage Return per Block