NAME

microsol-apc - Driver for APC Back-UPS BR UPS equipment

NOTE ABOUT HISTORIC NUT RELEASE

Note
Two NUT websites

This version of the page reflects NUT release v2.8.0 with codebase commited ff16dabca at 2022-04-04T11:04:28+00:00

Options, features and capabilities in current development (and future releases) are detailed on the main site and may differ from ones described here.

NOTE

This man page only documents the hardware-specific features of the microsol-apc driver. For information about the core driver, see nutupsdrv(8).

SUPPORTED HARDWARE

This driver supports the following UPS models:

  • APC Back-UPS BZ1500-BR

  • APC Back-UPS BZ2200I-BR

  • APC Back-UPS BZ2200BI-BR

In 2009, Schneider Electric acquired Microsol Technologies, and by 2012, the entire Microsol line was being sold under the APC brand. This driver supports these newer, APC-branded models. Older equipment should use solis(8).

EXTRA ARGUMENTS

This driver support the following extra optional settings in the ups.conf(5).

battext = n - (default = 0, no extra battery, where n = Ampere*hour )

prgshut = 1 - (default = 0, no programmable shutdown )

COMMANDS

  • shutdown.return - Shut down in .3 minutes and restart in .3 minutes

  • shutdown.stayoff - Shut down in .3 minutes and do not return

ISSUES

For other APC-Microsol models, the reported voltages, currents and power will be incorrect, as the communication protocol reports unprocessed data instead of real values, needing model-specific post-processing by the driver. Monitoring of UPS state (on-battery/on-line, critical battery) should work for other models, but is untested.

AUTHORS

SEE ALSO

The core driver:

Internet resources:

The NUT (Network UPS Tools) home page: http://www.networkupstools.org/