NAME
upslog - UPS status logger
SYNOPSIS
Note
|
Two NUT websites
This version of the page reflects NUT release v2.8.0 with codebase commited ff16dabca at 2022-04-04T11:04:28+00:00 Options, features and capabilities in current development (and future releases) are detailed on the main site and may differ from ones described here. |
upslog -h
upslog [OPTIONS]
DESCRIPTION
upslog is a daemon that will poll a UPS at periodic intervals, fetch the variables that interest you, format them, and write them to a file.
The default format string includes variables that are supported by many common UPS models. See the description below to make your own.
OPTIONS
- -h
-
Display the help message.
- -f format
-
Monitor the UPS using this format string. Be sure to enclose format in quotes so your shell doesn’t split it up. Valid escapes within this string are:
- %%
-
Insert a single "%"
- %TIME format%
-
Insert the time with strftime formatting
- %ETIME%
-
Insert the number of seconds, ala time_t. This is now a 10 digit number.
- %HOST%
-
insert the local hostname
- %UPSHOST%
-
insert the host of the UPS being monitored
- %PID%
-
insert the pid of upslog
- %VAR varname%
-
insert the value of variable varname
The default format string is:
%TIME @Y@m@d @H@M@S% %VAR battery.charge% %VAR input.voltage%
%VAR ups.load% [%VAR ups.status%] %VAR ups.temperature%
%VAR input.frequency%
- -i interval
-
Wait this many seconds between polls. This defaults to 30 seconds.
If you require tighter timing, you should write your own logger using the upsclient(3) library.
- -l logfile
-
Store the results in this file.
You can use "-" for stdout, but upslog will remain in the foreground by default.
- -F
-
upslog will run in the foreground, regardless of logging target.
- -B
-
upslog will run in the background, regardless of logging target.
- -s ups
-
Monitor this UPS. The format for this option is
upsname[@hostname[:port]]
. The default hostname is "localhost". - -u username
-
If started as root, upslog will setuid(2) to the user id associated with username for security.
If username is not defined, it will use the value that was compiled into the program. This defaults to "nobody", which is less than ideal.
SERVICE DELAYS
The interval value is merely the number given to sleep(3) after running through the format string. Therefore, a query will actually take slightly longer than the interval, depending on the speed of your system.
ON-DEMAND LOGGING
Sending a USR1 signal to a running upslog process makes it wake from the
current sleep and log immediately. This is useful when triggered from a
upssched event trigger (e.g. AT ONBATT
or AT ONLINE
) to ensure that an
entry always exists, even if the power goes away for a period of time shorter
than that specified by the -i
argument.
LOG ROTATION
upslog writes its PID to upslog.pid
, and will reopen the log file if you
send it a SIGHUP. This allows it to keep running when the log is rotated
by an external program.
SEE ALSO
Server:
Clients:
Internet resources:
The NUT (Network UPS Tools) home page: http://www.networkupstools.org/