Description

Here’s the information on the elusive APC smart signalling protocol used by their higher end units (Back-UPS Pro, Smart-UPS, Matrix-UPS, etc). What you see here has been collected from a variety of sources. Some people analyzed the chatter between PowerChute and their hardware. Others sent various characters to the UPS and figured out what the results meant.

RS-232 differences

Normal 9 pin serial connections have TxD on 3 and RxD on 2. APC’s smart serial ports put TxD on pin 1 and RxD on pin 2. This means you go nowhere if you use a normal straight through serial cable. In fact, you might even power down the load if you plug one of those cables in. This is due to the odd routing of pins - DTR and RTS from the PC usually wind up driving the on/off line. So, when you open the port, they go high and *poof* your computer dies.

Originally this evil hack was used to connect the UPS to the PC when this page was first being built. As you can see, I cheated and neglected the ground (only 2 wires!) and it still worked. This method can be used for playing around, but for professional systems this is obviously not a viable option.

That hack didn’t work out so well (damned cats), so it was retired quite awhile back. The most practical solution was to go out and BUY the DOS/Win version of Powerchute just for the black (smart) cable. I recommend doing the same thing if you actually care about this thing working properly. Of course, if you have one of the newer packages that came with PowerChute, you already have the cable you need.

Cable hacking

Redrawn 940-0024C clone diagram (D. Stimits)
Figure 1. Redrawn 940-0024C clone diagram (D. Stimits)
Mac 940-0024C clone diagram (Miguel Howard)
Figure 2. Mac 940-0024C clone diagram (Miguel Howard)
Original 940-0024C diagram (Steve Draper)
Figure 3. Original 940-0024C diagram (Steve Draper)

If you are handy with cable tools, check out these diagrams. They show how to clone the black "smart" cable that’s normally provided with APC models sold after 1996. The loopback pins (back to the PC) are used to keep PowerChute happy by allowing cable detection. If you use the NUT apcsmart or newapc drivers, those pins don’t matter.

The Smart Protocol

Despite the lack of official information from APC, this table has been constructed. It’s standard RS-232 serial communications at 2400 bps/8N1. Don’t rush the UPS while transmitting or it may stop talking to you. This isn’t a problem with the normal single character queries, but it really does matter for multi-char things like "@000". Sprinkle a few calls to usleep() in your code and everything will work a lot better.

Character Meaning Typical results Other info

^A

Model string

SMART-UPS 700

Spotty support for this query on older models

^N

Turn on UPS

n/a

Send twice with > 1.5s delay between chars

Only on 3rd gen SmartUPS and Black Back-UPS Pros

^Z

Capability string

(long string)

See "Capabilities" section for more info

A

Front panel test

Light show + "OK"

Also sounds the beeper for 2 seconds

B

Battery voltage

27.87

This obviously varies a lot based on the current charge.

Compare this to the nominal battery voltage

C

Internal temperature

036.0

Units are degrees C

D

Runtime calibration

!, then $

Runs until battery is below 25% (35% for Matrix)

This updates the j values - only works at 100% battery charge

Can be aborted with a second "D"

E

Automatic selftest intervals

336

Writable variable

Values:

  • 336 (14 days)

  • 168 (7 days)

  • ON (at power on) (note extra space)

  • OFF (never)

F

Line frequency, Hz

60.00

If this varies much, have a word with your local electrician

G

Cause of transfer

O

Writable variable

Values:

  • R (unacceptable utility voltage rate of change)

  • H (high utility voltage)

  • L (low utility voltage)

  • T (line voltage notch or spike)

  • O (no transfers yet since turnon)

  • S (transfer due to U command or activation of UPS test)

I

Measure-UPS: Alarm enable

FF

(not yet decoded)(bitmapped table, coming soon)

J

Measure-UPS: Alarm status

0F,00

(not yet decoded)(bitmapped table, coming soon)

K

Shutdown with grace period

OK

Send twice with > 1.5s delay between chars

Older units may send "*" instead of "OK"

Also see grace period

L

Input line voltage

118.3

Does not necessarily read 000.0 on line failure

M

Maximum line voltage

118.9

This is the max voltage since the last time this query was run

N

Minimum line voltage

118.9

Like the one above, this one also resets itself on every query

O

Output voltage

118.3

Also see on battery output voltage

P

Power load %

023.5

Relative to the capacity of the UPS

Q

Status flags

08

See status flags section for more info

R

Turn dumb

BYE

Only on 3rd gen Smart-UPS, Smart-UPS v/s, Back-UPS Pro

UPS must receive command to enter smart mode continue communications after sending this

S

Soft shutdown

OK

Command executes after grace period

UPS goes online when power returns

Only works when on battery

U

Simulate power failure

!, then $

See async notifier section for info on ! and $

V

Firmware revision

GWD

Can be used to determine abilities of hardware

W

Self test

OK

Tests battery, like pushing the test button on the front panel

Also see test results entry

X

Self-test results

OK

Values:

  • OK → good battery

  • BT → failed due to insufficient capacity

  • NG → failed due to overload

  • NO → no results available (no test performed in last 5 minutes)

Y

Enter smart mode

SM

This must be sent before anything else on this page will work.

Also see turn dumb command to exit smart mode

Z

Shutdown immediately

n/a

Send twice with > 1.5s delay between chars

UPS switches the load off immediately (no grace period)

a

Protocol info

(long string)

Returns three main sections:

Sections are separated with a period

b

Firmware revision

50.9.D

Decoding above info:

50

SKU (variable length)

9

firmware revision

D

country code (used in capability decoding)

c

UPS local id

UPS_IDEN

Writable variable

Up to 8 letter identifier for keeping track of your hardware

e

Return threshold

00

Writable variable

Minimum battery charge % to return from shutdown after power returns

Values:

  • 00 = 0% (UPS switches on immediately)

  • 01 = 15%

  • 02 = 25%

  • 03 = 90%

This prevents excessive cycling during multiple power failures

g

Nominal battery voltage

024

The battery voltage that’s expected to be present in the UPS normally

Compare to the actual voltage reading

f

Battery level

099.0

Percentage

It’s much easier to use this rather than doing math on the current battery voltage and the nominal battery voltage

h

Measure-UPS: Ambient humidity

042.4

Percentage

Only works on models with the Measure-UPS SmartSlot card

i

Measure-UPS: Dry contacts

00

Bitmapped hex variable

Component values:

  • 10 = contact 1

  • 20 = contact 2

  • 40 = contact 3

  • 80 = contact 4

j

Estimated runtime

0327:

Minutes

Must be calibrated to be effective

k

Alarm delay

0

Writable variable

Values:

  • 0 = 5 second delay after power failure

  • T = 30 second delay

  • L = alarm at low battery only

  • N = alarm disabled

Does not affect low battery warning

l

Low transfer voltage

103

Writable variable

See capabilities to get values for a UPS

UPS goes on battery after voltage drops below this point

m

Manufacturing date

11/29/96

Format may vary by country (MM/DD/YY vs DD/MM/YY)

n

Serial number

WS9643050926

Unique for each UPS

o

On-battery voltage

115

May be a writable variable on 220/230/240 VAC units

p

Shutdown grace delay

020

Writable variable - seconds

See capabilities to read values

Sets the delay before soft shutdown completes

q

Low battery warning

02

Writable variable - minutes

See capabilities to read values

The UPS will report a low battery this many minutes before it runs out of power

r

Wakeup delay

000

Writable variable - seconds

See capabilities to read values

The UPS will wait this many seconds after reaching the minimum charge before returning online

s

Sensitivity

H

Writable variable

See capabilities to read values

Meaning of values:

  • H → highest

  • M → medium

  • L → lowest

  • A → autoadjust (Matrix only)

u

Upper transfer voltage

132

Writable variable

See capabilities to read values

UPS goes on battery after voltage rises above this point

v

Measure-UPS: Firmware

4Kx

Firmware information for Measure-UPS board

t

Measure-UPS: Ambient temperature

80.5

Degrees C

Only works on models with the Measure-UPS SmartSlot card

x

Last battery change

11/29/96

Writable variable

This holds whatever the user sets in it, much like the UPS local id variable

y

Copyright notice

© APCC

Only works if firmware letter is later than O

z

Reset to factory settings

CLEAR

Resets most variables to initial factory values except identity or battery change date

Not on SmartUPS v/s or BackUPS Pro

-

Capability cycle

(various)

Cycle through possible capability values

UPS sends | afterward to confirm change to PROM

@nnn

Shutdown and return

OK

UPS shuts down after grace period with delayed wakeup after nnn tenths of an hour plus any wakeup delay time

Some older models send * instead of OK

0x7f

Abort shutdown

OK

Abort shutdown - use to abort @, S, K

Also known as the delete key in some places

~

Register #1

n/a

See register 1 table

'

Register #2

n/a

See register 2 table

7

Dip switch positions

n/a

See dip switch table

Only makes sense on models which actually have dip switches

8

Register #3

n/a

See register 3 table

9

Line quality

FF

Values

  • 00 → unacceptable

  • FF → acceptable

>

Battery packs

n/a

SmartCell models: returns number of connected packs

Non-SmartCell models: returns number set by user (use + and -)

[

Measure-UPS: Upper temp limit

NO,NO

Degrees C

Writable variable

Values: 55, 50, 45, …, 05 for both

Use - to enumerate through left side, + to enumerate through right side

]

Measure-UPS: Lower temp limit

NO,NO

Degrees C

Writable variable

See lower temp limit above

{

Measure-UPS: Upper humidity limit

NO,NO

%

Writable variable

Values: 90, 80, 70, …, 10 for both

Use - and + to change values

}

Measure-UPS: Lower humidity limit

NO,NO

%

Writable variable

Values: 90, 80, 70, …, 10 for both

Use - and + to change values

Matrix-UPS and Symmetra commands

^

Run in bypass mode

n/a

If online, "BYP" response is received as bypass mode starts

If already in bypass, "INV" is received and UPS goes online

If UPS can’t transfer, "ERR" received

<

Number of bad battery packs

000

Returns count of bad packs connected to the UPS

/

Load current

n/a

True RMS load current drawn by UPS

\

Apparent load power

n/a

Output load as percentage of full rated load

^V

Output voltage selection

n/a

Writable variable

Values:

  • A → Automatic (based on input tap)

  • M → 208 VAC

  • I → 240 VAC

^L

Front panel language

n/a

Writable variable

Values:

  • E → English

  • F → French

  • G → German

  • S → Spanish

  • Also 1, 2, 3, 4 → unknown

w

Run time conservation

n/a

Writable variable

Values:

  • NO → disabled

  • 02 → leave 2 minutes of runtime in battery

  • 05 → leave 5 minutes

  • 08 → leave 8 minutes

Dip switch information

Bit Switch Option when bit=1

0

4

Low battery alarm changed from 2 to 5 mins. Autostartup disabled on SU370ci and 400

1

3

Audible alarm delayed 30 seconds

2

2

Output transfer set to 115 VAC (from 120 VAC) or to 240 VAC (from 230 VAC)

3

1

UPS desensitized - input voltage range expanded

4 - 7

-

Unused at this time

Status flags

Some common things you’ll see:

  • 08 = on line, battery OK

  • 10 = on battery, battery OK

  • 50 = on battery, battery low

Bit Meaning

0

1 = runtime calibration occurring

Not reported by Smart UPS v/s and BackUPS Pro

1

1 = SmartTrim

Not reported by 1st and 2nd generation SmartUPS models

2

1 = SmartBoost

3

1 = on line

4

1 = on battery

5

1 = overloaded output

6

1 = battery low

7

1 = replace battery

Alert messages

Character Description

!

Line Fail - sent when the UPS goes on-battery, repeated every 30 seconds until low battery condition reached. Sometimes occurs more than once in the first 30 seconds.

$

Return from line fail - UPS back on line power, only sent if a ! has been sent.

%

Low battery - Sent to indicate low battery, but not on SmartUPS v/s or BackUPS Pro models

+

Return from low battery - Sent when the battery has been recharged to some level only if a % has been sent previously

?

Abnormal condition - sent for conditions such as "shutdown due to overload" or "shutdown due to low battery capacity". Also occurs within 10 minutes of turnon.

=

Return from abnormal condition - Sent when the UPS returns from an abnormal condition where ? was sent, but not a turn-on. Not implemented on SmartUPS v/s or BackUPS Pro models.

*

About to turn off - Sent when the UPS is about to switch off the load. No commands are processed after this character is sent. Not implemented on SmartUPS v/s, BackUPS Pro, or 3rd generation SmartUPS models.

#

Replace battery - Sent when the UPS detects that the battery needs to be replaced. Sent every 5 hours until a new battery test is run or the UPS is shut off. Not implemented on SmartUPS v/s or BackUPS Pro models.

&

Check alarm register for fault (Measure-UPS) - sent to signal that temp or humidity out of set limits. Also sent when one of the contact closures changes states. Sent every 2 minutes, stops when the alarm conditions are reset. Only sent for alarms enabled with I. Cause of alarm may be determined with J. Not on SmartUPS v/s or BackUPS Pro.

|

Variable change in EEPROM - Sent whenever any EEPROM variable is changed. Only supported on Matrix UPS and 3rd generation SmartUPS models.

Register 1

All bits are valid on the Matrix UPS. SmartUPS models only support bits 6 and 7. Other models do not respond.

Bit Meaning

0

In wakeup mode (typically lasts < 2s)

1

In bypass mode due to internal fault - see register 2 or 3

2

Going to bypass mode due to command

3

In bypass mode due to command

4

Returning from bypass mode

5

In bypass mode due to manual bypass control

6

Ready to power load on user command

7

Ready to power load on user command or return of line power

Register 2

Matrix UPS models report bits 0 - 5. SmartUPS models only support bits 4 and 6. SmartUPS v/s and BackUPS Pro report bits 4, 6, 7. Unused bits are set to 0. Other models do not respond.

Bit Meaning

0

Fan failure in electronics, UPS in bypass

1

Fan failure in isolation unit

2

Bypass supply failure

3

Output voltage select failure, UPS in bypass

4

DC imbalance, UPS in bypass

5

Command sent to stop bypass with no battery connected - UPS still in bypass

6

Relay fault in SmartTrim or SmartBoost

7

Bad output voltage

Register 3

All bits are valid on the Matrix UPS and 3rd generation SmartUPS models. SmartUPS v/s and BackUPS Pro models report bits 0 - 5. All others report 0 - 4. State change of bits 1, 2, 5, 6, 7 are reported asynchronously with ? and = messages.

Bit Meaning

0

Output unpowered due to shutdown by low battery

1

Unable to transfer to battery due to overload

2

Main relay malfunction - UPS turned off

3

In sleep mode from @ (maybe others)

4

In shutdown mode from S

5

Battery charger failure

6

Bypass relay malfunction

7

Normal operating temperature exceeded

Capabilities

Upon sending a ^Z, your UPS will probably spit back something like this (truncated here for the example):

#uD43132135138129uM43229234239224uA43110112114108 ....

It looks bizarre and ugly, but is easily parsed. The # is some kind of marker/ident character. Skip it. The rest fits this form:

  • Command character - use this to select the value

  • Locale - use b to find out what yours is, 4 applies to all

  • Number of choices - 4 means there are 4 possibilities coming up

  • Choice length - 3 means they are all 3 chars long

Then it’s followed by the choices, and it starts over.

Matrix-UPS models have ## between each grouping for some reason.

Acknowledgements

Large parts of this data were contributed or corrected by Steven Freed. This guy is some sort of APC UPS god. Many thanks.